(Panel Mount) Multifunction 3 Phase Protection Relay

Product: MPD-192

  • 3 Line – 3 Digit Display for Easy to Use and Understand 3 Phase Value
  • 3 Phase 3 Wire / 4 Wire Selectable
  • Display 3 Phase Voltage (Ph-Ph, Ph-N), 3 Phase Ampere & Frequency
  • Programmable Tripping Parameter
  • Single Instrument works for Both VAF Monitoring and Protection Relay
  • Programmable Relay 1 Relay 2 C/O
  • Fail Safe and Non Fail Safe Mode
  • RS-485 MODBUS Available as on request

INPUT:
Voltage AC
Direct Voltage AC 30 to 300V(L - N)
50 to 520V(L - L)
Burden < 0.2VA
Current AC
Primary CT Ratio 5 to 6000 Amp selectable
Secondary Current AC 0.1 to 5 Amp
Burden < 0.2VA
Overload Up to 6A continuous
Frequency 45.0 to 65.0 Hz
DISPLAY AND KEYS:
Display 3 Digit, 3 Line 7 Seg 0.56”,
RED LED
Keys Scroll, SET, RST, INC, DEC
DIMENSION:
Size (mm) 96 (H) X 96 (W) X 54 (D) mm
Panel Cutout (mm) 92 (H) X 92 (W) mm
Network Selection 3 Phase - 4 Wire,3 Phase - 3 Wire
TRIP SETTING:
Under Current 0.00 to CTR
Over Current 0.00 to CTR
Under Voltage 50 to 520V For 3Ø - 3W
30 to 300V For 3Ø - 4W
Over Voltage 50 to 550V For 3Ø - 3W
30 to 330V For 3Ø - 4W
Over / Under Frequency 45.0 to 65.0 Hz
Short Circut 1 - 9 Scale
Lock Rotor Point 0.5 to 9.0 Scale
Unbalance 5 - 60%
TIME PARAMETER:
Power On Delay 0 to 99 Sec
Initial Time Delay 0 to 99 Sec
Trip Delay Time(Voltage, Current, Frequency, SSP, Unbalance) 0 to 999 Sec
Scrolling Time 1 to 99 Sec
Reset Time 0 to 99 Sec
OUTPUT SPECIFICATION:
Relay 2 Nos
Relay Type 1st Relay ( NO - C - NC )
2nd Relay ( NO - C )
Rating 1st  Relay 10Amp, 230V AC (Resistive Load)
2nd Relay 5 Amp (With Simultaneous Actuation)
AUXILIARY SUPPLY:
Supply Voltage 100 to 270V AC, 50Hz
Power Consumption 4VA @ 230 AC MAX
ENVIRONMENTAL CONDITION:
Working Temperature 0 to 55°C
Storage Temperature 0 to 55°C
Relative Humidity 95 % RH Non-Condensing
Protection Level (As Per request) IP-65 (Front side As per IS/IEC 60529 : 2001)

  • Electrical Control Panel
  • Submersible Pump
  • Road Construction Panel
  • MCC Panel
  • Industrial Chiller And HV AC System
  • D.G. Set

Product Variant

Part Code

Voltage Input

Ampere Input

Other Input

RS-485 MODBUS 

Supply

MPD-192-E3-N0

30 to 300V AC (L-N), 50 to 520V AC (L-L)

60mA to 5A AC CT Selectable, CT Selectable up to 6000/5

 

 

100-270V AC/DC

MPD-192-E2-N0

30 to 300V AC (L-N), 50 to 520V AC (L-L)

60mA to 5A AC CT Selectable, CT Selectable up to 6000/5

 

 

50-550V AC

 MPD-19EL-E3-N0

30 to 300V AC (L-N), 50 to 520V AC (L-L)

60mA to 5A AC CT Selectable, CT Selectable up to 6000/5

ELR CBCT

 

100-270V AC/DC

MPD-192-E3-N7

30 to 300V AC (L-N), 50 to 520V AC (L-L)

Fixed Multispan 30A- 3 Ph CT Module

 

 

100-270V AC/DC

MPD-192-E3-N6

30 to 300V AC (L-N), 50 to 520V AC (L-L)

Fixed Multispan 60A- 3 Ph CT Module

 

 

100-270V AC/DC

MPD-192-E3-N8

30 to 300V AC (L-N), 50 to 520V AC (L-L)

Fixed Multispan 125A- 3 Ph CT Module

 

 

100-270V AC/DC

 MPD-19EF-E3-N0

30 to 300V AC (L-N), 50 to 520V AC (L-L)

60mA to 5A AC CT Selectable, CT Selectable up to 6000/5

EFR CBCT

 

100-270V AC/DC

MPD-192-M1-E3-N0

30 to 300V AC (L-N), 50 to 520V AC (L-L)

60mA to 5A AC CT Selectable, CT Selectable up to 6000/5

 

 

100-270V AC/DC

Reach Us

Reach out to us to receive more information, technical support, assistance, and more

Contact Us

Contact Sales

For any assistance or queries, please reach out to our support team. To get prompt solutions and address your concerns

Contact an expert

Solutions for Your Business

Looking for solutions to enhance your business? Look no further than Multispan! With our wide range of Products

Learn more

Visit our IIOT Site

Explore our IIOT site for solutions that connect machines, data, and people to optimize industrial processes and drive business growth.

Explore now

This site uses cookies and related technologies for site operation, analytics, and third party advertising purposes as described in our Privacy and Data Processing Policy. You may choose to consent to our use of these technologies or reject non-essential technologies. To opt-out of sharing with third parties information related to these technologies, select "Decline All".